Flint
Local Reviews
for Flint, MI
Was professional
Karen - Flint, MI 48503
program manager
Kelly - Flint, MI 48503
Great Services
Daniel - Flint, MI 48507-3007
Inspection
Haley - Flint, MI 48503
Response from Fire Pros | Fire Systems of MI | Adam's Fire :
Thank you for leaving your review! We greatly appreciate your feedback and are glad that we provided you valuable service! At your convenience, please consider sharing your experience on Google as well. https://tinyurl.com/yylegs7q Thanks again and have a fire safe day!
Great Service & Excellent Customer Service Skills
La - Flint, MI 48532
Mike was awesome from the time he entered the building. He was very friendly and had a great sense of humor!! Hope to see him visit our site again and again!! 🙂
Great as always!
Tamara - Flint, MI 48503
Always a pleasure!!
Response from Fire Pros | Fire Systems of MI | Adam's Fire :
Thank you for leaving a review, we greatly appreciate your feedback! Gerald is an awesome asset and we want to create value for you and your organization, Thanks again and have a fire safe day!
Great Service
Jodie - Flint, MI 48507
Very knowledgeable and I was shown stuff that I was not aware that we had to do.
Wonderful as always
Tamara - Flint, MI 48503
Very diligent employee, customer service orintated
unprepared
Patrick - Flint, MI 48503
The techs came here unprepared. When I had asked for the quote I made sure they knew they would need a street valve key. when they came they were clueless. They ended up having to call the city water dept to turn the water off.
Outstanding
Tamara - Flint, MI 48503
I was very pleased that the techs were careful to keep the ramp clean wile flushing the system. Construction was just completed - new paint etc.
Great services
James - Flint, MI 48507
Great Job
Tamara - Flint, MI 48503
Mark S.
Mark S.
John R.
Tyler H.
Trouble on NAC 3 is coming from a bad wire in between the horn strobe in room 120 and the horn strobe in room 119. Both rooms have a hard ceiling. To run a new wire we will need to make holes in the drywall and run wire across and then make drywall repairs. Each room is about 20'-25' to the hallway. Will need glow rods, and about 75’ of 14/2. *EOL is currently at the hornstrobe in rm 120 bedroom to keep the system from going in and out of trouble. Be sure to give notice to customer before we return for repairs so they can make sure rooms are vacant. - repair This quote is for 2 guys 1 day to get wire ran and fix the horn strobe circuit. Technician is to put an X on wall with pencil and have the facility cut opening wall locations and patch openings when wire run is completed .
Terrence J.
7/7/23 Confirmed with Brandon Yorks for 7/17/23 at 8:00am / DH Sent email regarding inspection DH Sprinkler Inspection Annual Fire Sprinkler Inspection (6 Wet, 1 Dry System) Full Flood Due: 2025 Deficiency for 4” Gem dry valve in closet in room 268, ITV in attic, attic access in room 269: Pressure relief valve on dry system air line failed. Pressure relief is currently plugged, need to replace. (1) 1/4” pressure relief Deficiency: A four-inch sprinkler main has a leak at a joint this joint will have to be replaced along with about 5 feet of the pipe. 3- 4” Victaulic couplings 5’ 4” pipe 1- 4” Victaulic 90 degree elbow One side of this pipe would have to be grooved in line in a very hot attic the other could be grooved on the floor you will need two men as this is considered confined space to complete this repair. If at all possible bring some boards to clear a path across to pipe that is leaking the rest of the attic has a walkway but this is deep into the attic and there are
Tyler H.
This quote is for fire alarm cellular monitoring. If an external antenna is needed an additional quote will be provided. Annual monitoring is $720.00 poor signal strength = add an antenna , then check with ED BEFORE leaving to confirm good signal strength.
Tyler H.
This quote is for 4 hours of additional troubleshooting time. If more time is needed contact customer for approval. Will need to return to finish tracking out NAC 3. I tracked it down the hallway on the 1st floor and then it goes into room 120, and then over to room 119, then to the hallway for the EOL. I moved the EOL to room 120 bathroom strobe to keep the system normal. We will need to return to track wiring from the 120 bathroom to the 119. Issue appears to be somewhere inside of that room. - repair
Terrence J.
Sprinkler Emergency Service Call Brandon called regarding a leak in the dry system / COntact on site will be Steve Clark 810-444-4075 please call with an ETA Deficiency: A four-inch sprinkler main has a leak at a joint this joint will have to be replaced along with about 5 feet of the pipe. 3- 4” Victaulic couplings 5’ 4” pipe 1- 4” Victaulic 90 degree elbow One side of this pipe would have to be grooved in line in a very hot attic the other could be grooved on the floor you will need two men as this is considered confined space to complete this repair. If at all possible bring some boards to clear a path across to pipe that is leaking the rest of the attic has a walkway but this is deep into the attic and there are no walkways.
George S.
George S.
Sean W.
David H.
David H.
Jason Z.
Annual Fire Alarm Inspection
Terrence J.
1/25/23 Material at Galloup / Jonah while TJ is in Allen Park you can go to Galloup. DH Sprinkler Repair A tech found leaks that are temporarily patched on the sprinkler piping in the attic. The attic entrance is between rooms 312 & 313. 2 1/2" sprinkler piping and fitting in the south attic will need to be replaced due to leaking.