Fire Pros | Fire Systems of MI | Adam's Fire | M&M | Elite Fire has completed 1 job in Westland, MI on February 12, 2024.
Fire Pros | Fire Systems of MI | Adam's Fire | M&M | Elite Fire has completed 8 jobs in Westland, MI in the last 12 months. The first job there was in June 2017.
Job Locations and Reviews
Terrence J.
2/8/24 Sent email regarding inspection DH 12/29/23MV Emailed Henry regarding inspection date 1/4, waiting on confirmation 12/13/23MV Henry confirmed Sprinkler Inspection Annual Fire Sprinkler Inspection (1 Wet System) Deficiency: There is no evidence of five-year internal obstruction investigation piping Red gasket material Deficiency: Sprinkler head box will need universal wrench 1- universal head wrench Deficiency: Fire department connection will need new stortz cap. 🧢 1- 4” stortz connection cap Deficiency: Sprinkler system is due for gauge change. 2- sprinkler gauges. Deficiency: There is no evidence of five-year fire department connection Hydro test. Red gasket material Deficiency: Alarm check valve has no evidence of five-year internal inspection. Red gasket material Deficiency: Fire department connection, check valve has no evidence of five-year internal inspection. Red gasket material Deficiency: Control valves, as well as inspectors test valve will need signs
Westland, MI 48185